Description
4 pole AC contactor relay, 65amps, 24V/110V/220V coil voltage for selection, 4P (4NO) or 4P (2NO+2NC) contact form. As a bypass contactor, it is widely used for long-distance connecting and breaking circuit.
Specifications
| Model | ATO-CJX2-65 | |
| Rated Operational Current (AC-3) | 380V | 65A |
| 660V | 42A | |
| Conventional Heating Current | 80A | |
| Rated Insulation Voltage | 690V | |
| Power of Controllable 3-phase Squirrel-cage Motor (AC-3) | 220V | 18.5kW |
| 380V | 30kW | |
| 660V | 37kW | |
| Operational Frequency (AC-3) | Electric Life | 600 times/h |
| Mechanical Life | 3600 times/h | |
| Service Life | Electric Life (104 times) | 60 |
| Mechanical Life (104 times) | 800 | |
| Matching Fusing Model | RT16-80 | |
| Average Power Consumption (20℃) @ 50Hz | Pick-up | 230VA |
| Holding | 32VA | |
| Unit weight(kg) | 4P (4N/O) | 1.32 |
| 4P (2N/O+2N/C) | 1.37 | |
| Ambient Temperature | -5℃~+40℃ | |
| Altittude | ≤2000m | |
| Rail Size | 75mm | |
| Class of Pollution | Class 3 | |
| Installation Category | Ⅲ |
Dimensions (unit: mm)
4P (4NO) AC contactor
4P (2NO+2NC) AC contactor
Tips: Coil overheating or burning, how to solve?
Possible Causes:
- The power supply voltage is too high or too low.
- Line technical parameters (such as rated voltage, frequency, load factor and applicable working system, etc.) do not match the actual use.
- Operating frequency is too high.
- Insulation damage due to poor coil manufacturing or mechanical damage.
- The moving part is stuck.
- The AC core is uneven or the magnetic air gap is too large.
- AC contactor derives the double coil of DC operation, because the normally closed interlocking contact welding does not release, and the coil is overheated.
Processing method:
- Adjust the power supply voltage.
- Exchange coils or contactors.
- Select other suitable contactors.
- Replace the coil to remove the obstacle that causes mechanical damage to the coil.
- Specially designed coils.
- Eliminate jamming.
- Clear the pole face or change the core.
- Adjust the interlocking contact parameters and replace the burnt coil.